ALSECURE® XFGB Cca 0,6/1kV

Products

XFGB Cca 7x1.5

Nexans ref. 10535898

  • Packaging: Cut to length (m)
  • Number of cores: 7
  • Conductor cross-section: 1.5 mm²

XFGB Cca 2x4

Nexans ref. 10556576

  • Packaging: Cut to length (m)
  • Number of cores: 2
  • Conductor cross-section: 4 mm²

XFGB Cca 2x16

Nexans ref. 10536294

  • Packaging: Cut to length (m)
  • Number of cores: 2
  • Conductor cross-section: 16 mm²

Description

Description

Standards

  • National
    NBN HD 604 Part 5/Sect.L

Application

Cca-s1,d2,a1 cable for installations inside buildings with high concentrations of people or expensive equipment especially in difficult evacuation conditions. Light armour to withstand some light mechanical impacts.

Design

  • Copper core, solid (Class 1) or stranded (Class 2)
  • Cross-linked polyethylene (XLPE) insulation (X)
  • Bedding halogen-free
  • Safety circuit with copper wires (*)
  • Steel tapes (F)
  • Oversheath in halogen-free thermoplastic material (G) - Colour: GREEN

(*) Cross-sectional area equal to the phase cross-section, with a maximum of 16 mm², may be used as earth conductor.

Installation

  • In cable duct
  • In cable tray
  • In open air if protected from direct UV rays
  • In industries
  • In houses
  • No direct burial, but can be installed underground in a correctly drained conduit
  • Operating temperatures down to -15°C are permitted, only if there are no mechanical forces nor movements.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
XLPE (chemical)
Material of bedding
Extruded compound
Armour type
Steel tapes
Outer sheath
Halogen free compound
Halogen free
Yes
Sheath colour
Green

Dimensional characteristics

Dimensional characteristics

Armour thickness
0.2 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U
0.6/1 kV
Test voltage
4 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Impact resistance Max (IEC 30364-5-51)
6 J
Mechanical resistance to impacts
Normal domestic use

Usage characteristics

Usage characteristics

Bending factor when laying
12 (xD)
Field of application
Indoor, Outdoor
Operating temperature, range
-15 - 60 °C
Minimum installation temperature
0 °C
Resistance to vibrations
Moderate
Chemical resistance
Medium
Water proof
Good
Metric marking
Continuous

Resources

Resources

Related families

Halogen free installation cables (unarmoured)

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close