Description
Installation cable with XLPE insulation, Cca s3 d2 a3, for domestic and industrial installations. Suited for indoor and outdoor use.
Standards
National : NBN HD 604 Part 4/Sect.GDeclaration of Performance : Reaction to fire: Cca-s3,d2,a3
according to EN50575:2014+A1:2016
Description
Design
- Copper core, solid (Class 1) or stranded (Class 2)
- Cross-linked polyethylene (XLPE) insulation (X)
- Filling compound or tape
- Fire-retardant PVC oversheath (V) - colour: Grey
Installation
- In cable duct
- In cable tray
- In open air if protected from direct UV rays
- Embedded in concret or cement or walls
- In industries
- In houses
- No ground laying without protection
- Operating temperatures down to -15°C are admitted, provided there are no mechanical forces nor movements.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Conductor flexibility | Solid class 1 |
Conductor shape | Circular solid (RE) |
Insulation | XLPE (chemical) |
Core identification | Blue, brown, black, grey, green / yellow |
With Green/Yellow core | Yes |
Material of filler / inner sheath | Compound or tape |
Outer sheath | PVC |
Sheath colour | Grey |
With smaller neutral conductor | No |
Dimensional characteristics | |
Number of cores | 5 |
Conductor cross-section | 1.5mm² |
Minimum outer sheath thickness | 1.09mm |
Average insulation thickness | 0.7mm |
Minimum outer diameter | 9.5mm |
Nominal outer diameter | 10.8mm |
Maximum outer diameter | 13.0mm |
Approximate weight | 183kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Test voltage | 4kV |
Permissible current rating in open air | 23A |
Mechanical characteristics | |
Impact resistance Max (IEC 30364-5-51) | 6J |
Usage characteristics | |
Bending factor when laying | 12(xD) |
Field of application | Indoor, Outdoor |
Max. conductor temperature in service | 90°C |
Operating temperature, range | -15 .. 60°C |
Minimum installation temperature | 0°C |
Resistance to vibrations | Moderate |
Water proof | Good |
Length | 2000m |
Packaging | Drum |
Metric marking | Continuous |
Docs and info
Related links
Selling information
- The international fire-retardant standard IEC 60332-3-24, corresponds to the belgian NBN C30-004-F2 standard.
- Maximum permissible current for single cores are given for installation in trefoil.
- Operating temperatures down to -15°C are admitted, provided there are no mechanical forces nor movements.