Alsecure XGB Cca 10G1.5

GTIN 5413404306169


Cca-s1,d2,a1
See all ALSECURE® XGB Cca 0,6/1kV / ALSECURE® XGB Cca 0,6/1kV EASY STRIPPABLE products
Description
ALSECURE XGB Cca has fire reaction class Cca-s1,d2,a1 according to EN 50575 and may be installed in bundle or side by side and in areas with increased fire risk according to AREI/RGIE. The cable is also suited for areas where AREI/RGIE imposes s1 a1.
Standards
National : NBN HD 604 Part 5/Sect.LDeclaration of Performance : Reaction to fire: Cca-s1,d2,a1
according to EN50575:2014+A1:2016
Description
NEW: Easy Strippable
The following construction are provided with the Easy Strippable feature:
• sections 1.5 - 2.5 mm² with 2 to 7 conductors
• sections 4 - 6 - 10 mm² with 2 to 5 conductors
Design
- Copper core, solid (Class 1) or stranded (Class 2) depending on cross-section
- Cross-linked polyethylene (XLPE) insulation (X)
- Filling compound or tape halogen-free
- Outer sheath in halogen-free thermoplastic material (G) - Colour: GREEN
Installation
- In cable conduit
- In cable duct
- Embedded in concrete, cement or walls
- In open air protected from direct UV rays
- In industries
- In houses
- Underground installation is allowed provided the cable is installed in a sufficiently drained tube
- Operating temperatures down to -15°C are permitted, only if there are no mechanical forces nor movements
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Conductor flexibility | Solid class 1 |
Conductor shape | Circular solid (RE) |
Insulation | XLPE (chemical) |
Core identification | Green/Yellow, black numbers |
With Green/Yellow core | Yes |
Material of filler / inner sheath | Compound or tape |
Outer sheath | Halogen free polyolefin |
Sheath colour | Green |
With smaller neutral conductor | No |
Dimensional characteristics | |
Number of cores | 10 |
Conductor cross-section | 1.5mm² |
Nominal outer diameter | 14.4mm |
Approximate weight | 310kg/km |
Electrical characteristics | |
Rated Voltage Uo/U | 0.6/1 kV |
Permissible current rating in open air | 14A |
Voltage drop, single phase | 25.0V/A.km |
Test voltage | 4kV |
Mechanical characteristics | |
Impact resistance Max (IEC 30364-5-51) | 6J |
Usage characteristics | |
Field of application | Indoor, Outdoor |
Bending factor when laying | 12(xD) |
Minimum installation temperature | 0°C |
Max. conductor temperature in service | 90°C |
Operating temperature, range | -15 .. 60°C |
Resistance to vibrations | Moderate |
Chemical resistance | Medium |
Water proof | Temporary |
Packaging | Cut to length |
Metric marking | Continuous |