SXAVB Cca 0,6/1kV

Description
SXAVB Cca is an armoured signalling cable for fixed low-voltage installations of 0.6/1kV outside and where there is a risk of mechanical damage. SXAVB Cca may be buried directly without additional mechanical protection. The cable is suitable for use at ambient temperatures between -20°C and + 60°C.
SXAVB Cca has fire reaction class Cca-s3,d2,a3 according to EN 50575 and may be installed in bundle or side by side according to the AREI/RGIE and in areas with increased fire risk.
Description
SXAVB Cca has fire reaction class Cca-s3,d2,a3 according to EN 50575 and may be installed in bundle or side by side according to the AREI/RGIE and in areas with increased fire risk.
Standards
National : NBN HD 603 Part 6/Sect.EDescription
Description
- Solid copper core
- XLPE conductor insulation (X)
- Filler sheath or tape banding
- Safety circuit in untinned copper wires (in case of steel tapes)
- Steel tapes or wires (A)
- Fire retardant PVC outer sheath (V) - grey (or black on special request)
Installation
- In houses
- In industries
- Underground installation with or without protection
- Open air laying
- Cable channels
- Cable ducts
- Only fixed installation
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Insulation | XLPE |
Material of filler / inner sheath | Compound or tape |
Outer sheath | Fire-retardant PVC |
Electrical characteristics | |
Rated Voltage Uo/U | 0.6/1 kV |
Mechanical characteristics | |
Mechanical resistance to impacts | Excellent |
Usage characteristics | |
Operating temperature, range | -20 .. 60°C |
Resistance to vibrations | No |
Water proof | Water splattering |
Minimum installation temperature | 5°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
Minimum Installation & Operating Temperature
Provided the conditions explained hereunder are respected, cables can be installed and operated at low temperatures down to -20°C:
Minimum Temperature during Installation
Ideally, the cable should not be installed at an ambient temperature below 5°C. If this is not possible, the cable must be kept in a heated room of at least 20°C for 24 hours. During installation, the temperature of the sheathing must be properly monitored. If it cools down too much (below 5°C), it must be warmed up again.Minimum Temperature during operation
The cable can operate at a minimum ambient temperature of -20°C, provided the following conditions are met:- the procedure for minimum temperature during installation has been respected
- the cable has been laid according to the rules of good practice and the bending radius has been scrupulously respected during installation
- the cable must not move at all after installation: no repositioning and certainly no exposure to vibrations.
Declaration of Performance
Declaration of Performance No: 1000495-BEDO
- Certification Date: 04/07/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 1+
- Notified body : NB 2658
- Declared performance: Reaction to fire Cca -s3,d2,a3 according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10537176 | SXAVB Cca 0.6/1kV 5x2,5 mm² | |
10538224 | SXAVB Cca 0,6/1 kV 12x2,5 mm² | |
10538225 | SXAVB Cca 0,6/1 kV 19x2,5 mm² | |
10538226 | SXAVB Cca 0,6/1 kV 27x1,5 mm² | |
10538227 | SXAVB Cca 0,6/1 kV 30x1,5 mm² | |
10538228 | SXAVB Cca 0,6/1 kV 37x1,5 mm² | |
10538229 | SXAVB Cca 0,6/1 kV 12x1,5 mm² | |
10538230 | SXAVB Cca 0,6/1 kV 19x1,5 mm² | |
10538231 | SXAVB Cca 0,6/1 kV 27x2,5 mm² | |
10538232 | SXAVB Cca 0,6/1 kV 37x2,5 mm² | |
10538233 | SXAVB Cca 0,6/1 kV 7x1,5 mm² | |
10538234 | SXAVB Cca 0,6/1 kV 7x2,5 mm² | |
10538235 | SXAVB Cca 0,6/1 kV 10x1,5 mm² | |
10538236 | SXAVB Cca 0,6/1 kV 24x1,5 mm² | |
10538237 | SXAVB Cca 0,6/1 kV 48x2,5 mm² | |
10538238 | SXAVB Cca 0,6/1 kV 61x2,5 mm² | |
10538239 | SXAVB Cca 0,6/1 kV 5x1,5 mm² | |
10538240 | SXAVB Cca 0,6/1 kV 10x2,5 mm² | |
10538241 | SXAVB Cca 0,6/1 kV 30x2,5 mm² | |
10538242 | SXAVB Cca 0,6/1 kV 40x1,5 mm² | |
10538243 | SXAVB Cca 0,6/1 kV 52x1,5 mm² | |
10538792 | SXAVB Cca 0.6/1kV 61x1,5 mm² |
Declaration of Performance No: 1000495-BEDO
- Certification Date: 27/10/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 1+
- Notified body : NB 2658
- Declared performance: Reaction to fire Cca -s3,d2,a3 according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10538793 | SXAVB Cca 0.6/1kV 48x1,5 mm² |