XFVB Cca 0,6/1kV
XFVB Cca 0,6/1kV
XFVB Cca is a lightly armoured installation cable for low voltage installations of 0.6/1kV with PVC outer sheath. XFVB Cca is used in domestic and industrial fixed installations presenting a risk of mechanical damage. XFVB Cca can be used both indoors and outdoors, provided it is shielded from direct sunlight. XFVB Cca may also be placed underground in a well-draining tube. The cable is not suited for direct burial. The cable is suitable for use at ambient temperatures between -15°C and + 60°C. The safety circuit under the armour is suitable for grounding conductors up to 16 mm2.
XFVB Cca has fire reaction class Cca-s3,d2,a3 according to EN 50575 and may be installed in bundle or side by side and in areas with increased fire risk according to AREI/RGIE.
XFVB Cca 0.6/1kV 2x1.5 B500 P1km
Nexans ref. 10538073
- Packaging: Drum (500m)
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 26 A
- Voltage drop, single phase: 25.0 V/A.km
XFVB Cca 0.6/1kV 2x1.5
Nexans ref. 10538060
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 26 A
- Voltage drop, single phase: 25.0 V/A.km
XFVB Cca 0.6/1kV 2x2.5
Nexans ref. 10538062
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 36 A
- Voltage drop, single phase: 15.4 V/A.km
XFVB Cca 0.6/1kV 2x2.5 B1000 P1km
Nexans ref. 10538074
- Packaging: Drum (1000m)
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 36 A
- Voltage drop, single phase: 15.4 V/A.km
XFVB Cca 0.6/1kV 2x2.5 B500 P1km
Nexans ref. 10538075
- Packaging: Drum (500m)
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 36 A
- Voltage drop, single phase: 15.4 V/A.km
XFVB Cca 0.6/1kV 2x2.5 R100 P2km
Nexans ref. 10538076
- Packaging: Ring (100m)
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 36 A
- Voltage drop, single phase: 15.4 V/A.km
XFVB Cca 0.6/1kV 2x4
Nexans ref. 10540657
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 4 mm²
- Permissible current rating in open air: 49 A
- Voltage drop, single phase: 9.7 V/A.km
XFVB Cca 0.6/1kV 2x6
Nexans ref. 10540659
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 6 mm²
- Permissible current rating in open air: 63 A
- Voltage drop, single phase: 6.5 V/A.km
XFVB Cca 0.6/1kV 2x10
Nexans ref. 10538070
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 10 mm²
- Permissible current rating in open air: 86 A
- Voltage drop, single phase: 4.0 V/A.km
XFVB Cca 0.6/1kV 2x16
Nexans ref. 10538081
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 16 mm²
- Permissible current rating in open air: 100 A
- Voltage drop, single phase: 2.2 V/A.km
XFVB Cca 0.6/1kV 2X25
Nexans ref. 10571229
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 25 mm²
- Permissible current rating in open air: 127 A
- Voltage drop, single phase: 1.5 V/A.km
XFVB Cca 0.6/1kV 3x1.5
Nexans ref. 10540643
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 3x1.5 B500
Nexans ref. 10540644
- Packaging: Drum (500m)
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 3x1.5 R100 P2km
Nexans ref. 10540646
- Packaging: Ring (100m)
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 3x2.5
Nexans ref. 10538083
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 3x2.5 B1000 P1km
Nexans ref. 10538063
- Packaging: Drum (1000m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 3x2.5 B500 P1km
Nexans ref. 10538077
- Packaging: Drum (500m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 3x2.5 R100 P2km
Nexans ref. 10538078
- Packaging: Ring (100m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 3x4
Nexans ref. 10540650
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 4 mm²
- Permissible current rating in open air: 42 A
- Voltage drop, single phase: 8.4 V/A.km
XFVB Cca 0.6/1kV 3x4 B1km
Nexans ref. 10540651
- Packaging: Drum (1000m)
- Number of cores: 3
- Conductor cross-section: 4 mm²
- Permissible current rating in open air: 42 A
- Voltage drop, single phase: 8.4 V/A.km
XFVB Cca 0.6/1kV 3x6 B1km
Nexans ref. 10540653
- Packaging: Drum (1000m)
- Number of cores: 3
- Conductor cross-section: 6 mm²
- Permissible current rating in open air: 54 A
- Voltage drop, single phase: 5.7 V/A.km
XFVB Cca 0.6/1kV 3x6
Nexans ref. 10540652
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 6 mm²
- Permissible current rating in open air: 54 A
- Voltage drop, single phase: 5.7 V/A.km
XFVB Cca 0.6/1kV 3x10
Nexans ref. 10540656
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 10 mm²
- Permissible current rating in open air: 75 A
- Voltage drop, single phase: 3.4 V/A.km
XFVB Cca 0.6/1kV 3X16
Nexans ref. 10538059
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 16 mm²
- Permissible current rating in open air: 100 A
- Voltage drop, single phase: 2.2 V/A.km
XFVB Cca 0.6/1kV 3x25
Nexans ref. 10540123
- Packaging: Cut to length (m)
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Permissible current rating in open air: 127 A
- Voltage drop, single phase: 1.5 V/A.km
XFVB Cca 0.6/1kV 4x1.5
Nexans ref. 10538079
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 4x1.5 B1000 P1km
Nexans ref. 10538061
- Packaging: Drum (1000m)
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 4x1.5 B500 P0.5km
Nexans ref. 10538080
- Packaging: Drum (500m)
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 21.6 V/A.km
XFVB Cca 0.6/1kV 4x2.5
Nexans ref. 10540647
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 4x2.5 R100 P2km
Nexans ref. 10540648
- Packaging: Ring (100m)
- Number of cores: 4
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 32 A
- Voltage drop, single phase: 13.3 V/A.km
XFVB Cca 0.6/1kV 4x4
Nexans ref. 10538009
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 4 mm²
- Permissible current rating in open air: 42 A
- Voltage drop, single phase: 8.4 V/A.km
XFVB Cca 0.6/1kV 4x6
Nexans ref. 10540654
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 6 mm²
- Permissible current rating in open air: 54 A
- Voltage drop, single phase: 5.7 V/A.km
XFVB Cca 0.6/1kV 4x10
Nexans ref. 10538071
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 10 mm²
- Permissible current rating in open air: 75 A
- Voltage drop, single phase: 3.4 V/A.km
XFVB Cca 0.6/1kV 4X16
Nexans ref. 10538057
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 16 mm²
- Permissible current rating in open air: 100 A
- Voltage drop, single phase: 2.2 V/A.km
XFVB Cca 0.6/1kV 4x25
Nexans ref. 10540122
- Packaging: Cut to length (m)
- Number of cores: 4
- Conductor cross-section: 25 mm²
- Permissible current rating in open air: 127 A
- Voltage drop, single phase: 1.5 V/A.km
XFVB Cca 0.6/1KV 7x1,5
Nexans ref. 10535696
- Packaging: Cut to length (m)
- Number of cores: 7
- Conductor cross-section: 1.5 mm²
- Permissible current rating in open air: 16 A
- Voltage drop, single phase: 25.0 V/A.km
XFVB Cca 0.6/1kV 7x2,5
Nexans ref. 10540574
- Packaging: Cut to length (m)
- Number of cores: 7
- Conductor cross-section: 2.5 mm²
- Permissible current rating in open air: 23 A
- Voltage drop, single phase: 15.4 V/A.km
Description
Description
Standards
-
NationalNBN HD 604 Part 4/Sect.G
Design
- Copper core, solid (Class 1) or stranded (Class 2)
- Cross-linked polyethylene (XLPE) insulation (X)
- Inner sheath
- Safety circuit with copper wires (*)
- Steel tapes (F)
- Fire-retardant PVC oversheath (V) - colour: Grey
(*)The cross-sectional area equal to the phase cross-section, with a maximum of 16 mm² may be used as earth conductor.
Installation
- In cable tray
- In cable duct
- In open air if protected from direct UV rays
- In industries
- In houses
- No ground laying without protection
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Related families
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania