ALSECURE® PLUS TEL 100/170 V

Send link to this page print Your Nexans contact on this page
ALSECURE® PLUS TEL 100/170 V CR1-C1-C2 F2-FR2-PH60
Fire Resistant Cables
Standards
National  NBN 713-020; NBN C30-004 cat. F2; NF C 32-310
Description

Application

ALSECURE® PLUS TEL cables are designed to be used in safety systems(emergency lights, warning systems, fire fighting equipments, etc ...) in all premises open to the public (concert hall, theaters, cinemas, department stores, hospitals, schools, etc ...), in high-rises buildings, in tunnels, in industries.

ALSECURE® PLUS TEL cables are installed in safety systems between buildings different. They are fire resistant and fire retardant, low smoke and halogen free: in the event of fire, emitted gases are non corrosive and have a very low toxicity.

Installation

ALSECURE® PLUS TEL cables will be installed to the wiring regulation and installation standards in force.

Laying temperature : in case of laying between 0°C and -10°C, warm up the cables in a heated room 48 hours minimum before installation.

Fire performance

  • Fire resistant according to NF C 32-070 Cat. CR1, EN 50200, NBN C 30-004 F2 FR2 60
  • Fire retardant according to IEC 60332 Part 2&1, NF C 32-070 Cat. C1 & C2, EN 50266, NBN C 30-004 F2
  • Low smoke : IEC 61034, EN 50268, NF C 32-073
  • Halogen free : IEC 60754, EN 50267, NF C 32-074
  • Low toxicity : IEC 60754, EN 50267, NF C 32-074
  • Low corrosivity : IEC 60754, EN 50267, NF C 32-074

Conductors laid up

Twisting in pairs or quads then assembled.

Pairs Identification

  • Core n°1 : Natural + black numbers
  • Core n°2 : Blue + black numbers

Marking

ALSECURE PLUS TEL n P 0.9 mm 100/170V NF C 32-310 CR1/C1 NF-USE* 205 F2 FR2 60

  • n= number of pairs
  • * for the cables ≤ to 10 pairs

 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Conductor flexibility Solid class 1  
Insulation Silicon elastomer  
Protection Tape (optional)  
Screen Copper tape  
Drain wire Copper  
Outer sheath Halogen free polyolefin  
Halogen free EN 50267  
Sheath colour Orange  
Dimensional characteristics
Conductor diameter 0.9mm  
Electrical characteristics
Rated Voltage Uo/U (Um) 100 / 170 V  
Mechanical characteristics
Cable flexibility Rigid  
Usage characteristics
Fire resistant CR1, NF C 32-070  
Fire retardant C1, NF C 32-070  
Flame retardant C2, NF C 32-070  
Smoke density EN 50268  
Gases toxicity Low toxicity to IEC 60754, EN 50267  
Gases corrosivity EN 50267  
Max. conductor temperature in service 90°C  
Operating temperature, range -20 .. 60°C  

 TOP
Your selection
Number of pairs  
Apply
Reset
Results   11/11
Select all Items Nexans ref. Name
10045366 ALSECURE® PLUS TEL 10P0.9 cut to length
10009356 ALSECURE® PLUS TEL 15P0.9 cut to length
10094071 ALSECURE® PLUS TEL 1P0.9 D1000 P4
10082547 ALSECURE® PLUS TEL 1P0.9 D500 P2
10045362 ALSECURE® PLUS TEL 1P0.9 cut to length
10094073 ALSECURE® PLUS TEL 2P0.9 D1000 P3
10082548 ALSECURE® PLUS TEL 2P0.9 D500 P2
10045363 ALSECURE® PLUS TEL 2P0.9 cut to length
10009234 ALSECURE® PLUS TEL 3P0.9 cut to length
10045364 ALSECURE® PLUS TEL 5P0.9 cut to length
10045365 ALSECURE® PLUS TEL 7P0.9 cut to length
Add to favorites

 TOP
complement

Type Approval

LCIE: Laboratoire Central des Industries Electriques

ISSEP: Université de Liège

 

Others design features

Electrical characteristics

  • DC loop resistance at 20 °C = 59.3 Ohm/km
  • Insulation resistance between conductors and screen (in the range 15 to 25 °C)

    (under U ≥ 200 V CC after 2 minutes minimum) = ≥500 MOhm.km

Bending Radius

  • r = 6 x maximum outer diameter

 TOP